Pt 100-Temperature relay Type TR600 RS485

Pt100 Temperature-Relay, interface RS485, 6 Sensors, 6 Limits, Digital display, easy programming

Share: Facebook   WhatsAppWhatsApp   E-Mail

Part number

T224361
with interface RS485

Approvals

Product description

 

The Pt 100 thermostat TR600 is a temperature controller and monitors up to six Pt 100 sensors at the same time. Six switching points and six relays permit almost any combination of switching action. It also can select the highest temperature of a group of three or six sensors. Programming is very variable and simple.

Due to the fact that 6 type Pt 100 sensors can be connected, the unit is especially suitable for temperature monitoring wherever up to 6 different measuring points must be monitored simultaneously:

  • motors and generators with simultaneous monitoring of bearings and coolant.
  • transformers with additional monitoring of the core temperature also.
  • power machines and plants

Approval
UL E377414 Process Control Equipment, Electrical - Component

Overview of functions

  • Measuring and monitoring range -199 ... +800 °C
  • 6 sensor inputs with 2- or 3-wire connection
  • 7 relay outputs with change-over contact
  • Alarm 1 … 6 relay K1 (11/12/14) ... K6 (61/62/64)
  • Sensor Error Relay K7 (71/72/74) monitors sensor break or sensor short circuit.
  • Interface RS485, protocols ZIEHL and modbus RTU
  • Universal power supply. 2 ranges AC/DC 24-60V or AC/DC 90-240 V
  • Universal power supply AC/DC 24-240 V
  • Terminal for USB-Stick for up- and downloads of sets of parameters and for firmware-updates
  • Accessory: Installation frame ER8 for panel mount
  • Alternative: Temperature Relay Type TR660IP

Displays

  • built-in 3 digit temperature display and 1 digit program-mode display
  • LED alarm showing state of the alarm relays
  • LED sensor error blinking at sensor short circuit or sensor interruption
  • Stored values of MIN- and MAX-temperature can be displayed
  • "Sensor select" showing temperatures of the different sensors
  • "Alarm select" showing switching points

Programmable for each relay extra:

  • hysteresis
  • electronic reclosing lock or autoresets
  • switch-on delay and switch-off delay
  • MIN or MAX-function of relay
  • relay releases or picks up when exceeding the setpoint

 

Technical data

Power Supply

Rated supply voltage Us

.......

AC/DC 24 – 240V

 

Tolerance

.......

DC 20,4 - 297 V,
AC 20 - 264 V 50/60 Hz

 

Power consumption

.......

< 4 W
< 13 VA

 

Sensor connection (6 sensors)

.......

Pt 100 (RTD) acc. to EN 60751 (2/3- wire)

 

Measuring range

.......

-199°C .. 800°C, resolution = 1°C

 

Resistance of sensor + wire.

.......

max. 500 Ohm

 

Sensor current

.......

≤0,7 mA

 

Measuring cycle/ time sensor

.......

≤ 1,5 s

 

Tolerance

.......

±0,5 % of measured value ±1 digit

 

Temperature factor

.......

<0,04°C/K

 

Relay output

K1 … K7

.......

7 x 1 change-over contacts (CO)

 

Switching voltage

.......

max. AC 415 V

 

Switching current

.......

max. 5 A

 

Switching capacity

.......

max. 1250 VA (resistive load)
max. 120 W at DC 24 V

 

UL electrical ratings

.......

250 V ac, 5 A, resistive

 

E214025

.......

240 V ac, 1/2 hp
120 V ac, ¼ hp
B 300 – pilot duty, UL 508

 

Nominal operational current Ie

AC15

.......

Ie = 3 A    .....  Ue = 250 V

 

DC13

.......

Ie = 2 A    .....    Ue = 24 V
Ie = 0,2    .....    A Ue = 125 V
Ie = 0,1    .....    A Ue = 250 V

 

Recommended fuse NO

.......

4 A time-lag or miniature circuit-breaker MCB B4

 

Recommended fuse NC

.......

3.15 A time-lag

 

Expected contact life mechanical

.......

3 x 107 operations

 

Expected contact life electrical

.......

1 x 105 operations at AC 250 V / 6 A

 

Test conditions (EN 61010-1)

Rated impulse voltage

.......

4000 V

 

Overvoltage category

.......

III

 

Contamination level

.......

2

 

Rated insulation voltage Ui

.......

300 V

 

On-time

.......

100%

 

EMC-tests (EN 61326-1)

emitted interference

.......

EN 61000-6-3

 

Burst

.......

EN 61000-4-4 +/-4 kV
Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms

 

SURGE

.......

90 x 35 x 58IEC 61000-4-5 +/-4 kV
Impulse 1,2/50 μs (8/20 μs)

 

discharge of static electricity

.......

IEC 61000-4-2 +/-4 kV contact,
+/- 8kV air

 

Environmental conditions

Ambient temperature range

.......

-20 °C ... +65 °C

 

Storage temperature range

.......

-20 °C … +70 °C

 

Altitude

.......

Up to 2000 m

 

Climatic conditions

.......

5 – 85 % rel. humidity, no condensation

 

External wiring temperature range

.......

-5 °C … +70 °C

 

Vibration resistance EN 60068-2-6

.......

2…25 Hz ±1.6 mm
25 ... 150 Hz 5 g

 

Galvanic insulation / Test-voltage

.......

Us – Relays, sensors, USB, analog output, Reset input -> DC 3820 V
Relays – sensors, USB, analog output, Reset input -> DC 3820 V

 

No galvanic insulation

.......

sensors, USB, analog output, Reset input

 

Reset input Y1/Y2

.......

app. DC 18 V / 3,5 mA

 

USB connector

.......

Type A, for connecting a USB stick
to configuration / to firmware update

 

Housing

Design / Installation Frame

.......

V8 / Front mounting kit ER8, 8 TE

 

Dimensions (H x W x D)

.......

140 x 90 x 58 mm, mounting height 55 mm

 

Line connection solid wire

.......

je 1 x 1,5 mm2

 

Stranded wire with isolated ferrules

.......

je 1 x 1,0 mm2​

 

Torque

.......

0,5 Nm (3,6 lb.in)

 

Protection class housing

.......

IP 20

 

Protection class terminals

.......

IP 20

 

Fitting position

.......

any

 

Mounting

.......

Snap mounting on 35 mm standard rail EN 60715 or M4 screws

 

Weight

.......

approx. 360 g

 

Downloads

Datasheet

Operating manual modbus

Operating manual RS485 (english)

Operating manual RS485 (russian)

Operating manual RS485 (french)