Electronic Current-Transducer Type STWA1AH
AC Electronic current transducer with analog output, Measuring transducer for AC currents
Product description
The STWA1AH is a current-transducer for AC currents 0...15 A. With the STWA1AH the value of a current can be evaluated very economically and space-saving.
The output-signal 0...20 mA can be evaluated or displayed with components with analog inputs, e.g. PLCs or ZIEHL TR 210, STW 1000 V2 or MINIPAN®.
For output-signal 4...20 mA choose our Electronic Current-Transducer Type STWA2AH
- current-proportional analog output DC 0...20 mA = AC 0...15 A (insulated)
- electrical connection via screw less pluggable terminals
- no supply voltage required
- DIN-rail-mount or with screws
- plug-in current transformer (Ø 11 mm)
- max. overload 100 A continuously, 300 A max. 10 s
Technical Data
Analog Output
Monitoring range
0...15 A
Analog output
DC 0...20 mA
Adjustment time
<0.5 s
Error (from 10% / Inom)
<5% from FS (at 100 Ω), <7% 50...200 Ω <9% ..300 Ω
Error with other load
5% / 100 Ω ( max.500 Ω)
Temperature coefficient
<0.06% / K
Ripple at 50 Hz
<2.5% at 300 Ω, <4.5% at 100 Ω, <7.5% at 50 Ω
Frequency
Functional range
30 ... 400 Hz
Nominal frequency
50 Hz
Error
≤ 0.2 % / Hz
Overload Capacity
continuously
100 A
max. 10 s
300 A
Test Conditions (EN 61010)
Rated impulse withstand voltage
4000 V
Overvoltage category
III
Pollution degree
2
Rated insulation voltage Ui
250 V
On-period
100 %
Rated ambient temperature range
0 ... 55 °C
EMC-immunity
EN 61326 (industrial electromagnetic environment)
EMC-emission
EN 61326 CISPR 11 class B
Vibration resistance EN 60068-2-6
2...25 Hz ±1.6 mm
25...150 Hz 5 g
Housing
Design
H
Dimensions (h x w x d)
50 x 36 x 56 mm
Wire connection
each 1 x 0.08 mm2 to 1.5 mm2
protection terminals
IP 20
Mounting position
any
Weight
app. 90 g
CAD Data
Certificates