Zero Export Device EFR4001IP
Relay for Energy Flow, optimization of self-consumption of self generated energy.
Zero Export Device.
Part number
Experience ZIEHL-Product live
Approvals
Product description
NEW: Zero Export Device Typ EFR4002IP
- You want to use 3 inputs for customary current transformers with secondary 1 or 5 A?
- You want to use medium-voltage applications and connect earthed medium-voltage transformers and series connected measuring devices?
- You want to comply with the German regulation "NELEV" and "EAAV"?
Then have a look at our new EFR4002IP!Relays for energy flow EFR4001IP monitor the current flow between public power grid and generating plant / consumer. Operation is made comfortably via integrated webserver or directly at the device. Measured values are displayed neatly arranged at device on monitor. When the own power plant generates more power than is actually consumed, rather than selling the excess energy to the grid provider, self-consumption is often more economical. This is especially reasonable when the difference is high between the price you pay to the grid provider and the price the provider pays for fed in energy.
Many areas suitable for photovoltaics could not be used so far, since only a limited amount of power can be fed in at the grid connection point. In Germany new standards allow exceeding this value by up to 2/3 (66.6%) installed capacity. The prerequisite for this is that the overbuilt power is consumed and not fed into the grid. In order to still ensure the stability of the system, this must be monitored. The same applies to zero export, when no energy at all may be fed into the grid. In this case, the device can be used as an energy flow direction sensor (EnFluRi). The EFR4001IP has been optimized for these functions.
Zero-Export-Device or limiter:
- Switching off the power generation system or parts of it if the permissible feed-in power is exceeded with relay K3
- Switching on consumers or reducing generators before it comes to that by means of regulating with an analogue output or switching loads with relays K1 and K2
- Energy flow direction sensor (EnFluRi sensor) and feed-in limitation < 0.1s
Functions
- Switching of up to 3 consumers: the largest consumer, ranked 1-2-3 or combination of 3 consumers (7 levels)
- Switch on and off points. At which energy flow consumers are switched on and off again
- Switch on and off delay of consumers, minimum on time.
- Control of heat pumps (SG-ready), battery chargers, inverters
- Switching on consumers or reducing generators before it comes to that by means of regulating with an analogue output or switching loads with relays K1 and K2
- Energy flow direction sensor (EnFluRi sensor) and feed-in limitation < 0.1s
Features
- Measuring of active power 1- or 3-phase ± 99,99 MW
- Pav,e monitoring predefined and with any values
- Pav,e monitoring in compliance with the entire limit curve
- 3 inputs for customary current transformers with secondary 1 or 5 A.
- Current transformer connectable, proportion adjustable
- Counters for power (feed in and consumption)
- 3 relay outputs
- 4 digital inputs Y1-Y4 for control signals, e.g. relay on or off
- IP-connection, integrated webserver
- Values available via Modbus TCP, SunSpec (Energy Meter)
- Analog outputs as measuring transducer and for stepless regulation of a consumer
Suitable current transformers:
- Usual current transformers up to 2,400 A, secondary 1 A or 5 A (for Pav,e min. class 1), e.g. ZIEHL type AS or WS
- CompactCTM7, 64/1 A, Kl. 1, 0,5 VA
- Split core KBR18S KBR18S, 60/1 A, Kl. 3, 0,4 VA (not for Pav,e)
Accessory:
Technical Data
Rated supply voltage
DC/AC 24 – 270 V 0/40...70 Hz, <3 W, <9 VA
Tolerance
DC 20,4 - 297 V
AC 20 - 297 V
Relay outputs K1, K2, K3
3 x 1 change-over contact
Switching voltage
max. AC 300 V, DC 300 V
Conventionel thermal current Ith
max. 9 A
Switching power max cos φ=1
2000 VA
Contact service life, electr. cos φ=1
105 operations at 300 V / 9 A
Rated operational current
AC-15 Ie = 6 A Ue = 250 V
Measurement of voltage (RMS)
L1 / L2 / L3 towardsN
Current transformer
adjustable 1:1 ... 1:250
Voltage phase-N
AC 10,0 … 330,0 V, 50/60 Hz
Resolution
0,1 V
Max. error of measurement
± 0,5% of fullscale, ±1 digit
Measurement of current
With transformers (scaleable up to 2.400 A)
Nominal currents / resolution
AC 1/5 A / 1 mA
Max. error of measurement
± 0,5% of fullscale, ±1 Digit
Overload capacity
6 A continously, 25 A max. 1 s
Resistance of input
60 mΩ
Measurement of active power
with voltage transformers from -99,99 up to 99,99 MW
Max. error of measurement
± 1 % of fullscale ±1 digit
Analog outputs
DC 0/4/1-10...20 mA, DC 0/2/0-5...10 V
Load
≤ 500 Ω
Test conditions
see general technical information
Operating temperature
-20 °C ... +55 °C
Housing
Design / Installation Frame
Design V8, Front mounting kit ER8, 8 TE
Dimensions (B x H x T)
140 x 90 x 58 mm, mounting height 55 mm
Protection housing/terminals
IP 30 / IP20
Attachment
on 35 mm DIN rail or with screws M4
Weight
app. 300 g