Universal-Relay Type TR800Web
Web-IO Universal-Relay, 8 Sensors/Inputs, DC Signals, Pt100, Thermoelements, 4 Limits, Web IO with Interface RS485, operation with browser via TCP/IP
Part number
Experience ZIEHL-Product live
Approvals
Product description
The TR800Web can be connected to the internet or an intranet and operated via TCP/IP from a normal PC with a suitable browser. No special software and no special instruction is necessary. The Universal-Relay TR800Web monitors and logs signals from up to 8 inputs. Up to 8 limits (one per input) can be programmed for each of the 4 output-relays. Thus e.g. alarm 1 can be activated when the temperature at a sensor (e.g. Pt100) at input 1 exceeds a limit or when the signal of a transmitter for pressure (e.g. 4-20 mA) at input 5 falls below a limit. It can also send an email when a limit is exceeded and/or when the signals falls short of the limit again. A day/night switchover allows to vary limits depending on daytime. In addition the device has an interface RS485 with the protocols Modbus and ZIEHL-standard.
>Accessory: Installation frame ER8 for panel mount
Applications
The TR800Web is used where one or more of the following features a required:
- measuring of up to 8 analog signals and transmit the data via TCP/IP
- reading of measured values and teleservice via internet/intranet
- signalling of alarms via email when limits are exceeded
- monitoring of filling level (water, gasoil) with ZIEHL filling level probe NS6123-6
- logging of measured values and remote inquiry e.g. for monitoring temperatures at engines and in plants
8 Measuring inputs (every input individually programmable)
- Pt 100, Pt 1000 in 2- or 3-wire connection
- KTY 83 or KTY 84
- Thermocouples type B, E, J, K, L, N, R, S, T
- DC 0-10 V, DC 0/4-20 mA
- Resistance 500 Ohm, resistance 30 kOhm
- Difference of 2 signals
4 Alarms
- 4 relays, potential-free change-over contacts
- Remote switching of relays via Ethernet
- or every alarm separately programmable
- one limit per input (limit and switching-back-value)
- second set of values switchable day/night
- switching-delay and switching-back delay
- remote operation of relays (on/off) with browser
- interlocked switching
- email at alarm
Programmable via internet in web-browser
- display of measured values, min- and max-values with date/time-stamp
- simulation of measured values
- state of alarms
- configuration of inputs (name, compensation, scaling and measuring-unit)
- configuration of alarms (limits, function of relays, ...)
- time-depending day/night changing of limits
- logging of up to 150.000 values per input, alarms with date/time-stamp
- logging-interval adjustable 2 seconds to 24 hours
- Alarmlogging
- configuration of network
- settings of system
- administration of users and code-protection
- real-time clock with synchronizing with time-server, reserve 7 days
Interfaces:
- Ethernet interface (http, https, UDP and Modbus)
- http (port can be selected and switched off) and https
- tp-upload for automatic (interval adjustable)
- storage of logged data on ftp-server
- UDP- and Modbus protocol to read data (port can be selected)
- AJAX for data-readout in html
- SNMP
- RS485 interface to readout data with modbus (RTU) and ZIEHL-protocol
Displays and Operating elements
- 8 LEDs for inputs
- 4 LEDs for alarms, 4 LEDs for state of relays
- 4 digit display for measuring values
- 3 buttons for reading measured values at the device and for setting of IP-adress
- switch IP 10.10.10.10 / user
- reset-button
- LEDs for activity of interfaces
Technical Data
Rated supply voltage Us
AC/DC 24-240 V
Tolerance DC
DC 20.4...297 V
Tolerance AC
AC 20...264 V
Power consumption
< 4 W, < 13 VA
Frequency
50-60 Hz
Relay output
4 x 1 changeover (CO)
Switching voltage
max. AC 415 V
Switching current
max. 5 A
Switching capacity
max. 1250 VA (ohmic load)
max.120 W at DC 24 V
UL electrical ratings
E214025
250 V ac, 5 A, resisitive
240 V ac, 1/2 hp
120 V ac, 1/4 hp
B 300 – pilot duty, UL 508
Nominal operational current Ie
AC15
Ie = 3 A ..... Ue = 250 V
DC13
Ie = 2 A ..... Ue = 24 V
Ie = 0,2 A ..... Ue = 125 V
Ie = 0,1 A ..... Ue = 250 V
Recommended fuses for contact
T 3,15 A (gL)
Expected contact life mechanical
3 x 107 operations
Expected contact life electrical
1 x 105 operations at AC 250 V / 6 A
Test conditions (EN 60 010-1)
Rated impulse voltage
4000 V
Overvoltage category
III
Contamination level
2
Rated insulation voltage Ui
300 V
On-time
100%
Environmental conditions
Ambient temperature range
-20 °C ... +65 °C
Storage temperature range
-20 °C … +70 °C
Altitude
Up to 2000 m
Climatic conditions
5 – 85 % rel. humidity, no condensation
External wiring temperature range
-5 °C … +70 °C
Vibration resistance EN 60068-2-6
2…25 Hz ±1,6 mm
25 ... 150 Hz 5 g
EMC-tests (EN 61326-1)
emitted interference
EN 61000-6-3
Burst
EN 61000-4-4 +/-4 kV
Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms
SURGE
IEC 61000-4-5 +/-1 kV
Impulse 1,2/50 μs (8/20 μs)
discharge of static electricity
IEC 61000-4-2 +/-4 kV contact,
+/- 8kV air
Network-connection
10/100 MBit Auto-MDIX
Max. number of connections
http/https = 5
Real-time clock
time-reserve 7 days
Reset input Y1/Y2
app. DC 18 V / 3,5 mA
RS 485 interface
Baud rate
4800, 9600, 19200 Baud
Parity
N, O, E (none, odd, even)
Wire length
1000 m at 19200 Baud
ZIEHL RS485 protocol
Time end request – start answer
5…50 ms
Send data without request 3 s
3 s ± 200 ms
Send data without request 170 ms
170 ms ± 50 ms
Sensor connection
Measuring-cycle / time depending on sensor type
Sensor(1+3+5+7)
0.340.. 3 s
Sensor(2+4+6+8)
0.340.. 3 s
Pt 100, Pt 1000 according to EN 60751
Tolerance
±0,5 % of measured value ±0,5 K (KTY ±5 K)
Sensor current
≤0,6 mA
Temperature drift
<0,04°C/K
Measuring time 2-wire connection
<= 220 ms
Measuring time 3-wire connection
<= 440 ms
Thermocouples according to EN 60 584, DIN 43 710
Temperature drift
< 0,01 % / K
Measuring error of the sensor wire
+0,25 μV / Ω
Reference junction
±5 °C
Measuring time
<= 440 ms
Voltage- / Current input
Temperature drift
< 0,02 %/K
Measuring time
<= 40 ms
Measuring of resistance
Precision 0,0 … 500,0 Ω
0,2 % of measured value ± 0,5 Ω
Precision 0…30,00 kΩ
0,5 % of measured value ± 2 Ω
Sensor-current
≤0,6 mA
Measuring time
<= 220 ms
Input S1 and S2
Maximum input voltage
30 V
Maximum input current
approx. 12 mA
Switching threshold
approx. 5 mA
Minimum pulse duration
> 25 ms
Auxiliary output voltage 18V 30mA
16-21 V max. 30 mA
Housing
Design / Installation Frame
V8, switchgear mount / Front mounting kit ER8, 8 TE
Dimensions (W x H x D)
140 x 90 x 58 mm, mounting height 55 mm
Wire connection, one wire
each 1 x 1,5 mm2
Stranded wire with insulated ferrules
each 1 x 1,0 mm2
Torque of screw
0,5 Nm (3,6 lb.in)
Protection class housing
IP 30
Protection class terminal
IP 20
Fitting position
any
Installation
Snap mounting on mounting rail 35 mm according to EN 60 715 or with screws M 4 (2 additional bars, not included in delivery)
Weight
app. 370 g
Downloads
Technical specifications
Applications / Hints
Certificates
FAQ / Product videos