Current-Sensor Type S1

Current sensor for AC- and DC currents, Put-on sensor with transistor output

Share: Facebook   WhatsAppWhatsApp   E-Mail

Part number

S225694
5-30 A adjustable

Product description

 

Recording of welding currents (mounting at ground wire) for controlling dedusting plants in combination with ZIEHL-controls type STW. Recording the state of a consumer of electricity (on or off or defective).

In general the current-sensor S1 is used where the current-flow is to be detected, with the exact value of the current either known from the power consumption of the connected consumer or does not matter for the evaluation.

For evaluation of measuring data in more than 1 cable, these outputs of several current-sensors can be connected in parallel (OR-evaluation).

  • switching point app. 5 A (option: adjustable 5-30 A)
  • monitoring of AC and DC currents
  • LED for current flow
  • mounting without disconnection of cable possible
  • 2 transistor-outputs, switching + and -, direct connection to a PLC possible
  • connection to current-relays ZIEHL type STW
  • robust, sealed execution
  • overload capacity: unlimited

 

Technische Daten

Rated supply voltage Us

.......

DC 24 V

 

Tolerance

.......

0,8 … 1,2 Us

 

current consumption

.......

max. 12 mA + max. 20 mA per output

 

current monitoring

Limit at Tu = 25°C

.......

AC/DC > 5…30 A

 

Tolerance

.......

± 20 %

 

Repeat accuracy

.......

± 2 %

 

Temperature dependence

.......

Typical < ±0,2 A / K Maximal < ±0,45 A / K

 

Frequency of measured current

.......

DC, AC 10 ... 400 Hz

 

Overload capacity, continuously

.......

500 A

 

Overload capacity, max. 1 minute

.......

1000 A

 

Switching-delay (on / off)

.......

ca. 300 ms

 

Indication of the switching

.......

LED yellow

 

Output PNP (Switching Plus)

output current

.......

≤ 20 mA

 

short circuit

.......

≤ 3 s

 

Output NPN (Switching Minus)

output current

.......

≤ 20 mA

 

short circuit

.......

≤ 3 s

 

electrical Safety (IEC/EN 61010-1)

Rated insulation voltage Ui

.......

300 V

 

Rated impulse voltage Uimp

.......

4000 V

 

Overvoltage category

.......

CAT III

 

Insulation material group I

.......

CTI = 600

 

Pollution degree

.......

3

 

Reinforced insulation

.......

Housing – input/output

 

Insulation test voltage type test

.......

AC 3510 V / 50 Hz, 60 s

 

EMC emitted interference (EN 61326)

RF radiated – EN 55011

.......

Class B

 

RF conducted – EN 55011

.......

Class B

 

EMC-tests (EN 61326)

ESD IEC/EN 61000-4-2

.......

±8 kV air

 

RF radiated IEC/EN 61000-4-3

.......

10V/m

 

Burst IEC/EN 61000-4-4

.......

2 kV

 

Surge IEC/EN 61000-4-5

.......

±1 kV

 

RF conducted IEC/EN 61000-4-6

.......

3V/m

 

Environmental conditions

temperature range

- operation

.......

0 °C … + 50 °C

 

- transport

.......

-25 °C … + 55 °C

 

- storage

.......

-25 °C … + 55 °C (70°C max. 24 h)

 

Altitude

.......

Up to 2000 m NN

 

climatic conditions

- environmental Class EN60721-3-3

.......

3K3

 

Humidity

- Damp heat (IEC60068-2-30)

.......

55 °C and 93% r.H.

 

Vibration

- Operation (IEC 60255-21-1) IEC 60068-2-6

.......

Class 2

 

- Transport (IEC 60255-21-1) IEC 60068-2-6

.......

Class 1

 

- Seismic IEC 60255-21-3)

.......

Class 1

 

Shock

- Operation (IEC 60255-21-2)

.......

Class 2

 

- Transport (IEC 60255-21-2)

.......

Class 1

 

Housing

Design

.......

S1

 

Dimensions (width x height x depth)

.......

16,5 x 11 x 102 mm

 

Housing material

.......

PC

 

Fire-protection class

.......

UL 94 V-0

 

Protection class housing

.......

IP64

 

Installation

.......

with 2 cable fasteners (included) or with 2x screws M3

 

installation position

.......

in accordance with current direction

 

Weight

.......

approx. 150 g including cable

 

Line connection (LiYY 4 x 0,34 mm2)

cable length

.......

2000 mm

 

ferrules

.......

8 mm

 

Downloads

Datasheet

Operating Manual