Electronic Current-Transformer Type STWA1SH
AC Electronic current transformer, fixed switching point
Product description
The STWA1SH is used where current flow has to be detected, with the exact value of the current either known from the power consumption of the connected consumer or does not matter for the evaluation.
The STWA1SH has an integrated electronics with transistor-output.
- isolated transistor-output max. DC 40 V / 40 mA
- output van be directly connected to a digital input of a PLC
- integrated diode for reverse voltage protection
- electrical connection via screwless pluggable terminals
- 2- wire, no supply voltage required
- DIN-rail-mount or with screws
- plug-in current transformer (Ø 11 mm)
- max. overload 100 A continuously, 300 A max. 10 s
Technical Data
Switching point at Tu = 25°C
AC 2 A +20/-40%
Hysteresis
approx. 6%
Repeat accuracy
±5 %
Temperature dependence
0...55°C: <0,5%/K (-20...0°C: <2,5%/K)
Overload cap. continous / 10s
100 A/ 300 A
Output voltage/current max.
DC 40 V / 40 mA
Voltage drop (ON)
max. 3 V
Leak current (OFF)
max. 0,6 mA
Switch-on/switch-off delay
ca. 50 / 200 ms
Nominal frequency
50 Hz
Operating range
30...70 Hz
Error
≤ 1 %/Hz
Rated ambient temperature range
-20°C…+55°C
Housing
Bauform H
Dimensions (hxwxd)
50 x 36 x 56 mm
Diameter for conductor
11 mm
Weight
ca. 90 g
CAD Data
Certificates
FAQ / Product videos