Current-Relay STW20V
Current Relay for AC-Detection, AND-Evaluation, 3 Transformers
Product description
The current relay STW20V monitors the current in up to 3 lines with current transformers STWA 1 (AND circuit). If there is a current in all 3 monitored lines, the relay (2 change-over contacts) picks up. If there is no current in at least one of the lines, the relay releases.
The relay works in closed circuit current. When voltage is applied to the STW, the relay signals an alarm until the it has picked up. This can be avoided if the device is constantly alive and monitoring is started by closing a contact at the Enable input. With a bridge at the Enable input, monitoring is automatically started when voltage is applied.
- 3 inputs (transformer STWA1)
- 3 x current-sensor S1 (powersupply required)
- AND-evaluation
- output relay 2 CO
- switching point app. AC 1 A
- Enable-input
- storage of alarms or Auto-Reset
- LEDs power on and alarm
- housing V4 for mounting on DIN-rail or wall-mount
Applications
Identifies power failure with 1- or 3-phase electrical consumers, e.g. with monitoring of heating elements or heating installations where a constant heating has to be guaranteed.
A further application is the identification of phase failure, monitoring of fuses, or triggering of operating hours counters.
Technical Data
Power supply Us
AC/DC 24 - 240 V, < 3 W, < 5 VA,
(AC 20 - 264 V, DC 20,4 - 297 V) AND-evaluation
Function
AND-evaluation
Transformer input
1 or 3, type STWA 1
Overload cap. continious/max.10s
100A / 300 A
Switching point on
≤ AC 1 A
Switching point off
≥ AC 0,3 A
Switch-off delay
approx. 0,3 s.
Switch-on delay
approx. 0,3 s.
Output relay
2 CO
Type of contact
type 2 see general technical informations
Testing conditions
see general technical informations
rated ambient temperature range
-20°C…+55°C
Dimensions H x B x T
Design V 4: 90 x 70 x 58 mm
Protection housing / terminals
IP 30 / IP 20
Weight
approx. 240 g
CAD Data
Certificates
FAQ / Product videos