Safety temperature limiter Type STR100
Safety Temperature Limiter for Pt100, SIL 2 according to IEC 61508
Part number
Product description
The Safety Temperature Limiter type STR 100 is an electronic thermostat monitoring the temperature of heating equipment and machinery. When the permitted temperature-limit is exceeded or in case of a malfunction, the STR 100 switches off without delay. An active reset must be made for a restart. The temperature limit is adjustable with a scaled potentiometer. An unintended or unauthorized adjusting of the limit is prevented through a lead-sealed transparent cover.
With supply voltage switched on, the STR 100 operates in a changeable lockout mode and the relay must be started by a reset (manually with built-in reset button or external reset) to make contact (no) close. Applicable for plants with supervised operation. The mode of operation corresponds to type 2BJK according EN 60730/VDE 0631.
The temperature is measured with a Pt 100 resistance temperature detector (RTD) according to EN 60751 / IEC 751. The process qualification in combination with the sensor must be proved. To fulfil affords for higher safety functionality the function has to be routine-tested periodically. The thermostat series STR 100 meets safety category 3 (Safety of machines EN 954-1, TÜV Rheinland documents T 24/00 + T103 2007 Z1 + T103 2007 E2). If safety approval is recommended only use listed RTD.
Temperature Limiter
A temperature-limiter is an equipment that switches of permanently (locked) after the limit has been exceeded. A reset (manually or with a tool) is possible after the temperature has fallen below switch-back point (limit minus hysteresis).
Safety Temperature Limiter
A safety temperature limiter is a limiter that fulfils in addition the requirements of extended safety according to DIN 3440.
Technical Data
Rated supply voltage Us
AC 230 V
DC 24 V
Tolerance voltage
50 / 60 Hz
Power consumption
< 2 W
Internal fuse
T 0.16 A time-lag (or slow blow 0.25 A)
Sensor connection
2-wire Pt 100 RTD according EN 60751/IEC 751
α = 0.00385
Terminal current max.
< 3.15 mA
Terminal voltage max.
< 15 V open terminals
< 2 V with Pt 100 and highest temperature
Line compensation
0.5 Ώ normally
Release function
Temperature limit
Accuracy
Hysteresis
10 °C (±25 %)
Reset
internal reset button or contact (no) Y1, Y2
Temperature factor
0.2 K/10 °C
Relay output 11, 12, 14
Alarm
1 co contact, closed current circuit principle
Switching voltage
max. AC 400 V max. DC 300 V
Switching current
max. 6 A
Switching power (resistive load)
max. 2000 VA max.48 W at DC 24 V
Rated operational current Ie
2 A AC15 400V
2 A DC13 24 V
3 A AC15 230V
Recommended Fuse
4 A quick acting
Mechanical contact life
3 x 107 operations
Electrical contact life
1 x 105 operations with 230 V/6 A
Factor of reduction at cos. ϕ = 0.3
0.5
Relay output 21, 22
Alarm
1 nc contact, operating current principle
Switching characteristic minimum
12 V 10 mA AC/DC
* We recommend an RS-Suppressor to avoid high voltage spikes when a contactor is connected.
Reset push-button Y1, Y2
1 no, potential-free
Switching characteristic minimum
1 V 1 mA DC
Testing conditions (EN 50178, EN 61010-1, EN 60947-5)
Rated insulation voltage Ui
AC 250 V
Contamination level
2 (normal)
Rated impulse voltage
4000 V
Overvoltage category
III
EMC - Interference resistance
EN 61000-6-2, EN 61326
EMC - Interference transmission
class B, EN 61326
On period
100 %
max. ambient temperature
0...50 °C EN 600068-2-2 Dry Heat
Housing
Design
built-in type, pluggable
Material
Housing ....... PA 6.6
Socket ....... PA 6.6 GF25
Flame Class
UL 94 V-2
UL 94 HB
Dimensions (H x W x D)
82 x 42 x 121 mm
Line connection solid wire
1 x 2.5 mm2
Stranded wire with ferrules
1 x 1.5 mm2
Degree of protection (IP-Code)
Housing ....... IP 40
Socket....... IP 20
Fitting position
any
Mounting
35mm standard rail EN 60715 or with M4 screws
Vibration resistance
1 mm at 25 Hz
10 g at 25 …100 Hz
Shock resistance
10 g for 20 ms, 20 g for 4 ms
Weight
app. 300 g