Zero Export Device EFR4002IP

 

Relay for Energy Flow, optimization of self-consumption of self generated energy.
Zero Export Device.

 

Share: Facebook   WhatsAppWhatsApp   E-Mail

Part number

S227260

Approvals

CE EC Declaration of Conformity

See certificates

EAAV / NELEV (coming)

Product description

 

NEW:

  • Can be used for medium-voltage applications Connection of earthed medium-voltage transformers and series connected measuring devices
  • For the German regulation "NELEV" and "EAAV"

     

     

    Relays for energy flow EFR4002IP monitor the current flow between public power grid and generating plant / consumer. Operation is made comfortably via integrated webserver or directly at the device. Measured values are displayed neatly arranged at device on monitor. When the own power plant generates more power than actually is consumed it often is more economical to consume the excess energy self. This is especially reasonable when the difference is high between the price you pay to the grid provider and the price the provider pays for fed in energy.

     

    Many areas suitable for photovoltaics could not be used so far, since only a limited amount of power can be fed in at the grid connection point. In Germany new standards VDE-AR-N 4105:2018-11 allow exceeding this value by up to 66.6% or more installed capacity. The prerequisite for this is that the overbuilt power is consumed and not fed into the grid. In order to still ensure the stability of the system, this can be monitored with EFR4002IP. The same applies to zero export, when no energy at all may be fed into the grid. In this case, the device can be used as an energy flow direction sensor (EnFluRi). The EFR4002IP has been optimized for these functions.

     

    Zero-Export-Device or limiter:

    • Switching off the power generation system or parts of it if the permissible feed-in power is exceeded with relay K3
    • Switching on consumers or reducing generators before it comes to that by means of regulating with an analogue output or switching loads with relays K1 and K2
    • Energy flow direction sensor (EnFluRi sensor) and feed-in limitation < 0.1s

    Functions

    • Switching of up to 3 consumers: the largest consumer, ranked 1-2-3 or combination of 3 consumers (7 levels)
    • Switch on and off points. At which energy flow consumers are switched on and off again
    • Switch on and off delay of consumers, minimum on time.
    • Control of heat pumps (SG-ready), battery chargers, inverters

     

    Suitable current transformers:

    • Current transormers scaleable up to 2.400 A, secondary 1 A or 5 A (for Pav,e min. class 1) for example ZIEHL Type AS or WS
    • Compact CTM7, 64/1 A, Kl. 1, 0,5 VA

    Accessory:

     

    Technical Data

    Rated supply voltage

    .......

    DC/AC 24 – 270 V 0/40...70 Hz, <3 W, <9 VA

     

    Tolerance

    .......

    DC 20,4 - 297 V
    AC 20 - 297 V

     

    Relay outputs K1, K2, K3

    .......

    3 x 1 change-over contact

     

    Switching voltage

    .......

    max. AC 300 V, DC 300 V

     

    Conventionel thermal current Ith

    .......

    max. 9 A

     

    Switching power max cos φ=1

    .......

    2000 VA

     

    Contact service life, electr. cos φ=1

    .......

    105 operations at 300 V / 9 A

     

    Rated operational current

    .......

    AC-15 Ie = 6 A Ue = 250 V

     

    Measurement of voltage (RMS)

    .......

    L1 / L2 / L3 towardsN

     

    Current transformer

    .......

    adjustable 1:1 ... 1:250

     

    Voltage phase-N

    .......

    AC 10,0 … 330,0 V, 50/60 Hz

     

    Resolution

    .......

    0,1 V

     

    Max. error of measurement

    .......

    ± 0,5% of fullscale, ±1 digit

     

    Measurement of current

    .......

    With transformers (scaleable up to 2.400 A)

     

    Nominal currents / resolution

    .......

    AC 1/5 A / 1 mA

     

    Max. error of measurement

    .......

    ± 0,5% of fullscale, ±1 Digit

     

    Overload capacity

    .......

    6 A continously, 12.5 A max. 1 s

     

    Resistance of input

    .......

    30 mΩ

     

    Measurement of active power

    .......

    with voltage transformers from -99,99 up to 99,99 MW

     

    Max. error of measurement

    .......

    ± 1 % of fullscale ±1 digit

     

    Analog outputs

    .......

    DC 0/4/1-10...20 mA, DC 0/2/0-5...10 V

     

    Load

    .......

    ≤ 500 Ω

     

    Test conditions

    .......

    see general technical information

     

    Operating temperature

    .......

    -20 °C ... +55 °C

     

    Housing

    Design / Installation Frame

    .......

    Design V8, Front mounting kit ER8, 8 TE

     

    Dimensions (B x H x T)

    .......

    140 x 90 x 58 mm, mounting height 55 mm

     

    Protection housing/terminals

    .......

    IP 30 / IP20

     

    Attachment

    .......

    on 35 mm DIN rail or with screws M4

     

    Weight

    .......

    app. 300 g

     

Downloads

Datasheet

Quick Guide

Operating Manual

Operating Manual Modbus

Operating Manual SunSpec Modbus TCP