Relay for Voltage and Frequency UFR1002IP
Grid- and Plant Protection VDE-AR-N 4105, 4110, 4120, IP Interface and LCD-Display, Measuring Voltage up to 1,200 V with the ZIEHL VG1200 coupling device
Part number
Experience ZIEHL-Product live
Approvals
CE EC Declaration of Conformity
See certificates
EAAV / NELEV (coming)
Product description
NEW: For the German regulation "NELEV" and "EAAV"
The grid decoupling relay UFR1002IP is the "big brother" of the UFR1001E and monitors voltage and frequency in three-phase and AC grids.
With a color LCD display (German/English) and joystick, it is even easier to operate than the UFR1001E. Measured values and settings are clearly displayed. The device can be programmed, updates installed and the alarm memory read out via the integrated IP interface. The real-time clock (with power reserve) simplifies the traceability of the alarms. Up to 1,200 V can be monitored in conjunction with the VG1200 coupling device. The device has a two-channel, single-fault-safe design and thus meets the requirements of VDE-AR-N 4105:2018-11. The function of the connected switch is monitored. If monitoring is activated, the device does not switch on again if a switch-off error is detected.
Limit values for different applications are preset. Where permitted, they can easily be changed. If the nominal voltage is changed, the device automatically adjusts the limit values. With the standby input, a remote shutdown can be implemented, e.g. with a ripple control receiver.
Monitoring of
- Under/over voltage 15-520V (with ZIEHL VG1200 coupling device up to 1,200 V)
- Under/over frequency 45-65 Hz
- Voltage quality (10-minute average)
- Vector shift 2-65°
- ROCOF, rate of change of frequency df/dt 0.100...5.000 Hz/s
- Zero voltage U0 (ANSI 59v0)
- passive anti islanding protection
Features:
- single-fault-proof, with monitoring of connected switch (can be switched off when using the integrated switch of PV and battery converters
- Programmable restart attempts in the event of a switch-on error in the connected switch
- Relay K3 with programmable functions, including life contact, delayed switch-on signal for switches or error messages
- Response time adjustable 0.05 … 300,0 s
- Switch-back time adjustable 0 … 6,000 s
- Preset according to VDE-AR-N 4105-2018-11 (Pr 1.02, Pr 1.08 + 1.09) and VDE-AR-N 4105-2011-08 (Pr 1.01)
- Preset according to VDE-AR-N 4110-2018-11 (Pr 1.11-1.14) and bdew guideline (Pr 1.03-1.06)
- automatic adjustment of the switching points when the nominal voltage is changed
- Alarm counter for 100 alarms (with trigger value, cause and date/time, time of restart)
- 3 programmable digital inputs
- Standby counter and timer with standby on/off date/time
- Test and simulation function with measurement of switch-off times
- Sealing option and code protection for settings
- Interface ethernet TCP/IP, values available via modbus TCP
- Simple commissioning and programming thanks to preset basic programs and transmission via IP interface
- Supply voltage AC/DC 24-270 V
- Housing for DIN-rail-mount, 105 mm wide, mounting height 66 mm
- Accessory: Installation frame ER6 for panel mount
Accessory
Certificates
- Germany:
Certificate of conformity Grid- and Plant protection acc. to VDE-AR-N 4105 2018-11 "Plants for generation of own energy in low voltage grid" - Certificate for component VDE-AR-N4110 and 4120
- Great Britain:
Certificate of compliance G98/1-7:2022 and G99/1-9:2022 - Austria:
Clearance Certificate TOR Producer Type A and TOR Producer Type B - Sweden nät och systemskydd:
Certificate of compliance EN 50549-1:2019. EN 50549-2:2019
Further certificates in preparation
Technical Data
Power supply
Rated supply voltage Us
AC/DC 24-270 V, 0/50/60 Hz, <4.5 W, < 12 VA
DC: 20,4...297 V, AC: 20,4...297 V
Bridging at dropping Us
230 V -> 0 V: 1.2 s
Relay output
3 change-over contacts (see operating manual)
Voltage
Measurement phase - phase
AC 15...530 V (< 5 V display: 0)
Measuring voltage phase - neutral
AC 10...310 V (< 5 V display: 0)
Setting range
AC 15...520 V
Measurement method
true RMS
Measurement accuracy
≤ 0.8% of nominal voltage
Measurement functions
3-phase with / without neutral
Switching delay (dAL)
adjustable 0,05 (± 15ms)...300,0 s
Switching back delay (doF)
adjustable 0 (> 200 ms)...6.000 s
Input resistance phase-phase and phase-N
993kΩ
Frequency
Measurement range
40...70 Hz
Setting range
45,00...65,00 Hz
Measurement accurance
± 0.05 Hz
Switching delay (dAL)
adjustable 0,05 (± 15ms)...300,0 s
Switching back delay (doF)
adjustable 0 (>200 ms)...6.000 s
RoCoF df/dt
Setting range
0,100...5,000 Hz/s, 4...50 cycles
Digital inputs
E1/E2, Y0...Y2, In1...In3
DC 15...35 V
Test Conditions (IEC/EN 60255)
Rated impulse voltage
4000 V
Overvoltage category
III
Pollution degree
2
Rated insulation voltage Ui
300 V
Operating time
100 %
Operating temperature
-20 °C...+55 °C
Storage temperature
-25 °C...+70 °C
Climatic conditions (IEC/EN 60721-3-3)
3K5 (except condensation and formation of ice)
EMC - immunity
EN 61 000-6-2
EMC - emission
EN 61 000-6-3
Housing
Design / Installation Frame
Design V6 / Front mounting kit ER6
Dimensions h x b x d
90 x 105 x 58 [mm], mounting height 55 mm
Protection Housing / Terminals
IP30/20
Attachment
DIN-rail 35 mm according to EN 60 715 or screws M4
Weight
approx. 290 g
Applications / Hints
Updates
Firmware (Update, version 12690-1420-04)
Program 1.11 (Update, Version 01)
Program 1.12 (Update, Version 01)
Program 1.13 (Update, Version 01)
Program 1.14 (Update, Version 01)
Program 1.20 (Update, Version 01)
Program 1.21 (Update, Version 01)
Program 1.22 (Update, Version 01)
Program 1.23 (Update, Version 01)
Program 2.00 (Update, Version 01)
Program 2.01 (Update, Version 01)
Program 2.02 (Update, Version 01)
Program 2.10 (Update, Version 01)
FAQ / Product videos