If the connected current transformers are grounded at higher measuring voltages, the device measures only about half the power. This is due to the design of the measuring inputs.
As a remedy, intermediate transformers with suitable accuracy and power are connected before the measuring inputs of the EFR4001IP, 5/5 A or 5/1 A (e.g. MBS WSK 30, part numbers 30013 or 30211).

EFR4001IP with firmware version 12720-1410-03 may experience the following problem:
- If program 9 or 10 is selected and
- the device is disconnected from the supply voltage for longer than 7 days,
- then a reset loop (device briefly switches on and then off again) may occur after the supply voltage is reconnected.

Remedy:
- Press the joystick button of the EFR4001IP upwards for >2sec,
- This takes you to the reset menu, which is displayed for 2min.
- During this time the device can be reached via the website.
- On the web page, a program <9 must be selected under Configuration.
- After that, the device is accessible again and starts as usual.

A firmware update (version 12720-1410-04) is available for download.