Pt 100-Temperature relays Type TR111V
Pt 100 Temperature-Relay, 1 sensor Pt 100, 3-wire, 1 Limit, 3 measuring ranges
Product description
Temperature-Relays TR111V can be used as limit-switches or 2-point controllers with high repeat accuracy. 3 measuring-ranges, adjustable hysteresis and switching delay and the choice between operating- and closed-current principle of the relay make it a very universal device.
Application: Protection from over-temperature in processes, plants and machines. Monitoring of temperatures in bearings. Controlling of temperatures in processes and plants.
Overview of Functions
- Measuring input 1x Pt 100 (RTD)/ 3-wire
- Measuring ranges selectable:
– -10...+40/ 0...100/ 0...200 °C
– 0...100/ 0...200/ 200...300/ 300...400 °C - 1 limit adjustable 0...100 %
- switching delay adjustable 0,1...10 s
- Output-relay 1 changeover-contact (co)
- Operating- or closed-current-mode selectable with bridge
- Switching off at sensor-shortcircuit or break
- LEDs for display state of relay
- Housing for mounting in switchgear cabinets or fuseboxes, 35 mm wide
- Mounting heigt 55 mm
- Universal supply-voltage AC/DC 24-240 V
Technical data
Rated supply voltage Us
AC/DC 24 - 240 V, 0/50/60 Hz, < 2 W, < 3 VA
(DC 20.4 - 297 V, AC 20 - 264 V)
Pt 100 Sensor (RTD)
EN 60715 / IEC 60751
Measuring ranges
ranges selectable
Error of setting
± 5 K
Repeat error
app. 0,5 K
Temperature-dependence
≤ 0,05 %/K
Hysteresis
adjustable 2...10 K
Switching delay don/doff
adjustable 0,1...10 s
Output relay
1 change-over-contact (co)
Type of contact
Type 3 (see general technical information)
Test conditions
see general technical information
Rated ambient temperature range
-20...+55 °C
Dimensions h x w x d
Design V4: 90 x 70 x 58 [mm], mounting height 55 mm
Attachment
on 35 mm DIN rail according to EN 60 715 or screws M4
Protection Housing/Terminals
IP30/IP20
Weight
approx. 100 g
CAD Data
FAQ / Product videos