Niveaurelais NS20
Level Monitor for conductive liquids, 1 Niveau, 1 oder 2 Limits, MIN / MAX-control, adjustable sensitivity, Housing Design V2 for circuit-breaker-box
Product description
Level-Relays NS 20 for conductive liquids can be used as monitors for 1 Level and for controlling a level between 2 electrodes.
- 3 elektrodes for MIN/MAXcontrol
- 2 elektrodes (E2 open) as level monitor
- Sensitivity adjustable 5 kΩ…250 kΩ
- LED for state of relay
- Function of relay reversible (picks up or releases at top electrode)
- Switching-delay adjustable 0,1…10 s
- Housing 35 mm wide, mounting height 55 mm
- Universal supply-voltage AC/DC 24-240 V
Application level monitor
Protection from running dry or overflow, monitoring of pumps for leaks, detection of leaks.
Application Min/Max
Controlling a level between minimum (elektrode E2) and maximum (E3). As long as E3 is dry, a magnetic valve is opened (or a pump is running) and liquid is influenting. As soon as maximum (E3) is reached, the NS 20 closes the valve. When the level falls below E2, the cycle starts new. In reverse also discharging of a container can be controlled.
Overview of functions example filling with 2 electrodes
The detection of the level is made with a DC-free measuring of resistance between all electrodes The common electrode in E 1. A magnetic valve that is switched with relay-contacts 15-18 opens and lets liquid in until the upper electrode E3 is in contact with the liquid. Then the relay releases (15-18 open) and the valve closes. The relay remains released as long as electrode E 2 is in contact with the liquid. When the level falls below E2, the relay picks up (LED Relay on, 15-18 close) and the procedure starts new with opening the valve. Thus thelevel of the liquid is kept between E 1 and E 2.
For monitoring one level only or in applications to protect from running dry or overflow or leak detection, only electrodes E1 and E3 are connected.
Technical Data
Supply voltage Us
AC/DC 24 – 240 V ...... 0 / 50 / 60 Hz < 3 W < 5 VA
Tolerance
DC 20,4 - 297 V ...... AC 20 - 264 V
Level-electrodes (E1 , E2 , E3)
max. voltage
< 6 Veff
max. current
<250 μA
Switching point
adjustable app. 5 kΩ ... 250 kΩ
Switching point 5 kΩ
max. cable-length 2500 m ...... max. capacity of cable 500 nF
Switching point 250 kΩ
max. cable-length 50 m ...... max. capacity of cable 10 nF
Switch on-/off-delay
0,1...10sec adjustable
Tolerance
25%
Data of relay (EN 60947-5)
Type of contact
1 change-over-contact (CO)
Switching voltage
max. AC 415 V
Switching current
max. 6 A
Switching power
max. 2000 VA (ohmic load)
max. 120 W bei DC 24 V
Rated nominal current Ie for co
3 A AC15 250 V ...... 2 A DC13 24 V
Recommended fuse
3,15 A slow ( gL )
Contact life mechanical
3 x 107 operations
Contact life electrical
1 x 105 operations at 240 V / 6 A
1 x 106 operations at 240 V / 2 A
Reduction factor at cosϕ = 0,3
0,5
UL electrical ratings
250 V ac, 3 A, general use
240 V ac, 1/4 hp, 2.9 FLA
120 V ac, 1/10 hp, 3.0 FLA
C 300
Test conditions (EN 50178 / EN 60 947 safe insulation)
Rated impulse withstand voltage
4000 V
Contamination level
3
Rated insulation voltage Ui
250 V
On-period
100 %
Rated ambient temperature range
-20 °C ... +60 °C (EN 60068-2-1 dry heat)
Interference resistance
EN 61000-6-2
Interference transmission
EN 61000-6-3
Vibration resistance (EN 60068-2-6)
2…25 Hz ±1,6 mm
25 ... 150 Hz 5 g
Housing
Design
V2
Mounting height
55 mm
Dimensions (B x H x T)
each 1 x 4 mm2
Stranded wire with wire-end sleeves
each 1 x 2,5 mm2
Protection housing
IP 30
Protection terminals
IP 20
Attachment
Snap-mount on DIN-rail 35 mm according to EN 60 715 or screws M4
Weight
app. 130 g
Downloads
Technical specifications
CAD Data
Certificates
FAQ / Product videos