Phase Sequence-Change Relay DRR20
Phase Sequence-Change Relay with integrated monitoring of undervoltage and asymmetry
Product description
Phase-Sequence-Change Relays DRR20 measure the sequence of the phases and switch – if necessary the rotation of the field. At the output (connect relays K1 and K2 in series in this application) two contactors are connected. The contactor at the normally-open contact of K2 switches the phases 1:1without changing them, the second (atnormally-closed contact) changes 2 phases.
When switching on with phasesequence ok, relay K2 picks up. With wrong phase-sequence it remains released. After K2 has switched, K1 picks up. K1 also releases first. This makes sure, that no wrong contactor can be picked up under any condition. Additionally the DRR20 monitors the three phases for asymmetry and undervoltage. If the limits are exceeded, the K1 switches off (respectively doesn't pick up) and protects the connected motor from damage. The device can also be used as a monitor for undervoltage, asymmetry or phase-sequence.
Applications are machines and equipment that is operated at variable locations, e.g. at building sites. Pumps, compressors and vacuum-cleaners always
run correctly and they are protected from damage by undervoltage or asymmetry.
- automatic change of wrong phase-sequence when connected falsely (2 contactors afforded)
- running backward of motors is avoided
- no switching on at asymmetry or undervoltage
- relay K2 picks up when phase-sequence is correct
- relay K1 picks up (after K2) when symmetry and voltage is correct
- 3 LEDs for state of relays and errors
- measuring-voltage 3 AC 400 V
- limit asymmetry adjustable 5…25 %
- limit undervoltage adjustable 70…95 %
- alarm-delay adjustable 0,1…10 s (undervoltage and asymmetry)
- no supply-voltage required
Technical Data
Rated supply voltage Us
3-phase, 400 V without N
Admissible tolerance Us
+20%...-30%
Output relay
ca. 3 VA
Type of contact
50/60 Hz
Output relay
2 change-over contacts (co)
Type of contact
type 2 see general technical informations
Test conditions
see general technical informations
Rated ambient temperature range
-20°C...+55°C
Limit asymmetry
adjustable 5...25 %
Limit undervoltage
adjustable 70...95 %
Hysteresis
app. 2%
Delay undervoltage/asymmetry
adjustable 0,1...10 s
Delay phase-loss (<60% Us)
< 0,2 s
Pick-up delay after recovery of Us
< 0,5 s
Delay K2 - K1
app. 100 ms
Housing
Dimensions (h x w x d) mm
housing K: 75 x 22,5 x 115 mm
Fitting position
any
Attachment
on 35 mm DIN rail according to EN 60715 or 2 screws M 4
Protection housing / terminals
IP 30 / IP 20
Weight
150 g