Universal-Measuring Transducer/ Isolating Amplifier Type MU100U
Universal Measuring Transducer / Isolating Amplifier
Product description
The universal measuring transducer MU100U can be connected to any supply voltage AC or DC between 24 and 240 V. Input signals and output signals are electrically isolated from each other. Signals DC 0/4-20 mA or 0-10 V can be connected to the inputs. The input signals are transduced to standard-signal 0-10 V, 0/4-20 mA at the outputs.
The measuring signal applied to one of the inputs is converted into a normalized voltage signal and changed into a frequency. The frequency signal is transferred by means of an optocoupler for electrical isolation. It is then converted again into a voltage and amplified. Signals 0/4-20 mA and 0-10 V are now available at the outputs. The electronics before and after the optocoupler are supplied from the power supply unit with potential separated voltages each.
It is often necessary to separate the potentials of signals by means of isolation amplifiers as otherwise this would lead to adulteration of measuring values because of compensating currents. Furthermore, the low-voltage side is effectively protected against damage caused by malfunctions at the primary side. Because of the variety of the current standard signals (0-20 mA, 4-20 mA, 0-10 V), it often happens that the output of a measuring transducer is not compatible with the input of the evaluation unit. MU 100 U eliminates these problems. Stockkeeping is largely facilitated by the universal supply voltage and different input and output signals in one device. These measuring transducers almost always fit.
- Input signals DC 0 - 20 mA, 0 - 10 V
- Output signals DC 0 - 20 mA, 0 - 10 V
- Offset with signals 4 - 20 mA can be compensated by the user
- Universal supply voltage AC/DC 24 - 240 V
- electrical isolation between inputs and outputs
- supply voltage for external measuring transducers -5/+18 V/ max. 30 mA
- Isolation voltage 2.5 kV
Technical Data
Power Supply
Rated supply voltage Us
AC/DC 24V - 240V
adm. tolerance DCV
DC 20 - 297 V
adm. tolerance ACV
AC 19 - 264 V, Frequenz 20 - 120 Hz
Power consumption
< 3 W
recommended fuse
2 A slow (gL)
Inputs
Input voltage
DC 0 - 10 V
DC 0 - 10 V
> 500 kΩ
Input current
DC 0/ 4 - 20 mA
max. current
DC 50 mA
Nominal input resistance
50 Ω
Voltage supply for ext. Measuring Transducer
voltage
DC -5 V/ ground GND1 -16 - 20 V
current
max. 30 mA
Outputs (2 outputs with common ground)
Output voltage
DC 0 - 10 V
max. no load voltage
DC 12 V
Load
> 1 kΩ
Output current
DC 0/4 - 20 mA
max. short-circuit current
DC 30 mA (short-circuit-proof)
max. load
500 Ω
Accuracy
class 0,2 at Tu = 23°C
Temperature effect
0,025%*K-1
Nominal rise time T0,9
50 ms
Operation Conditions
rated ambient temperature range
0…50°C
ambient storage temperature
-20…+70°C
Test Conditions
Isolation
Input/Output/Supply voltage 2500 VAC
EMV
EN 61000-6-4 / EN 61000-6-2
Operating time
100%
Housing
Dimensions H x B x T
Design K: 75 x 22,5 x 110 [mm]
Line connection one-wire
1 x 0,5 - 2,5 mm2
fine-wire with multicore cable ends
1 x 0,14 - 1,5 mm2
Fitting position
any
Fastening
Snap mounting on 35 mm standard rail conforms to DIN EN 60 715 or M4 screws
Protection housing / terminals
IP 40 / IP 20
Burning behaviour
UL 94 V-2
Stripping length
8 mm
Connection torque of screw
max. 0,5 Nm
Weight
ca. 200 g