Trafosafe TS1000
Relay for Transformer-Protection with integrated fan control, direct connection up to 6 fans
Product description
The Trafosafe TS1000 is applied at transformers with forced cooling. It monitors the temperature of the transformer with 3 sensor-circuits (PTC-thermistors), controls the forced cooling depending on the load of the transformer, reports exceeding of alarm-temperature and switches off the transformer (trip) when increasing of the temperature continues.
Up to 6 fans can be controlled and monitored directly with the TS1000. Contactors and motor protection switches are not necessary any more.
At Pt 100-monitored transformers the TS1000 can be used to control only the fans.
Temperature-Monitoring
- 1 PTC-circuit for controlling the cooling (1T1/1T2) = input for starting fan when using as fan-control only
- 2 x 1 PTC-circuit for alarm 1 (2T1/2T2) and alarm 2/trip (3T1/3T2), monitored for short-circuit and interruption
- Alarm1 (K2) in closed-circuit current mode = monitoring of function
- Alarm 2/trip (K3) in open-circuit current mode = no signal/tripping when switching on the device
- Test-/Reset-button for testing the function
Fan-Control and Monitoring of fan
- direct connection of up to 6 fans 0.07...4.0 A
- automatic exceeding of the on-time of the fans at high load of the transformer
- Monitoring of failure fan (over-/undercurrent)
- Self-calibration of the monitored values of the currents to the fans
- Switching-point for current-failure adjustable ± 5-40%
- automatic test of fans 1-30 days, disconnectable
- Relay for reporting fan-failure
- Clear displays with LEDs
General
- Universal Power Supply AC/DC 24-240 V
- compact housing for cabinet-mount, 140 mm wide, mounting heigt 55 mm
- Attachment on 35 mm standard rail or with 3 screws M4
Technical data
Rated supply voltage Us
AC/DC 24 - 240 V 0/45-120 Hz <2W <4 VA
Tolerance
DC 20,4-297 V, AC 20-264 V
Connectable PTC-circuits
5 x 1...6 Pcs according to DIN VDE V 0898-1-401 (formerly DIN 44081/82)
Switching point
< 4000 Ω
Output relays K2, K3, K4
3 x 1 change-over-contact (co)
Type of contact
Type 2 (see general technical information)
Output relays 1-6
6 x 1 normally-open contact (no)
Rated current of fans
0.07...4.0 A
Test conditions
see general technical information
Rated ambient temperature
-20...+55 °C
Dimensions h x w x d
Design V8: 90 x 140 x 58 [mm], mounting height 55 mm
Attachment
on 35 mm DIN rail according to EN 60 715 or 3 screws M4 (option)
Protection Housing/Terminals
IP30/IP20
Weight
approx. 400 g
Certificates
FAQ / Product videos