Pt 100-Temperature Relay Type TR400

Pt 100 Temperature-Relay, 4 Sensors, 4 Limits, digital, 2 analog outputs

Share: Facebook   WhatsAppWhatsApp   E-Mail

Part number

T224380

Approvals

Product description

 

The Pt 100 thermostat TR400 is a temperature controller and monitors up to 4 Pt 100 sensors at the same time. 4 switching points and 4 relays permit almost any combination of switching action. It also can select the highest temperature of a group of2,  3 or 4 sensors. The temperatures of two sensors or groups of sensors can be issued to 2 analog outputs i.e. for remote displays or further evaluation. Programming is very variable and simple.
Due to the fact that 4 type Pt 100 sensors can be connected, the unit is especially suitable for temperature monitoring wherever up to 4 different measuring points must be monitored simultaneously:

  • motors and generators with simultaneous monitoring of bearings and coolant.
  • transformers with additional monitoring of the core temperature also.
  • power machines and plants

Overview of functions

  • Measuring and monitoring range -199 ... +800 °C
  • 4 sensor inputs with 2- or 3-wire connection
  • 4 relay outputs K1 to K4 with change-over contact
  • Sensor Error Relay K7 monitors sensor break or sensor short circuit as well as an
  • interruption of the power-supply.
  • 2 analog outputs, 0/4...20 mA und 0/2...10 V, with individual scaling.
  • Universal power supply AC/DC 24-240 V
  • Terminal for USB-Stick for up- and downloads of sets of parameters and for firmware- updates
  • Accessory: Installation frame ER8 for panel mount
  • Alternative: Temperature Relay Type TR660IP

 

Technical data

Rated supply voltage Us

.......

AC/DC 24-240 V

 

Tolerance DC

.......

DC 20.4...297 V

 

Tolerance AC

.......

AC 20...264 V 50/60 Hz

 

Power consumption

.......

< 4 W, < 13 VA

 

Sensor connection

4 sensors

.......

Pt 100 (RTD) acc. to EN 60751 (2/3- wire)

 

Measuring range

.......

-199°C .. 800°C, resolution = 1°C

 

Resistance of sensor + wire

.......

max. 500 Ohm

 

Sensor current

.......

≤0,7 mA

 

Measuring cycle/ time sensor

.......

≤ 1,5 s

 

Tolerance

.......

±0,5 % of measured value ±1 digit

 

Temperature factor

.......

<0,04°C/K

 

Analog outputs

Analog outputs

.......

OUT 1 and OUT 2

 

Voltage-output

.......

DC 0/2 V – 10 V, max. DC 10 mA

 

Current output

.......

DC 0/4 mA – 20 mA

 

Load

.......

max. 500 Ω

 

No-load voltage

.......

max. DC 16 V

 

Tolerance

.......

1% of programmed span ±1 °C

 

Relay-Data K1 … K4 and K7

5 x 1 change-over contacts

Switching voltage

.......

max. AC 415 V

 

Switching current

.......

max. 5 A

 

Switching capacity

.......

max. 1250 VA (resistive load)
max. 120 W at DC 24 V

 

UL electrical ratings

.......

250 V ac, 5 A, resistive

 

E214025

.......

240 V ac, 1/2 hp
120 V ac, ¼ h
B 300 – pilot duty, UL 508

 

Nominal operational current Ie

AC15

.......

Ie = 3 A  ......  Ue = 250 V

 

DC13

.......

Ie = 2 A     ......  Ue = 24 V
Ie = 0,2 A  ......  Ue = 125 V
Ie = 0,1 A  ......  Ue = 250 V

 

Recommended fuse NO

.......

4 A time-lag or miniature circuit-breaker MCB B4

 

Recommended fuse NC

.......

3.15 A time-lag

 

Expected contact life mechanical

.......

3 x 107 operations

 

Expected contact life electrical

.......

1 x 105 operations at AC 250 V / 6 A

 

Test conditions (EN 61010-1)

Rated impulse voltage

.......

4000 V

 

Overvoltage category

.......

III

 

Contamination level

.......

2

 

Rated insulation voltage Ui

.......

300 V

 

On-time

.......

100 %

 

EMC-tests (EN 61326-1)

emitted interference

.......

EN 61000-6-3

 

Burst

.......

EN 61000-4-4 +/-4 kV
Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms

 

SURGE

.......

IEC 61000-4-5 +/-4 kV
Impulse 1,2/50 μs (8/20 μs)

 

discharge of static electricity

.......

IEC 61000-4-2
+/-4 kV contact, +/- 8kV air

 

Environmental conditions

Ambient temperature range

.......

-20 °C ... +65 °C

 

Storage temperature range

.......

-20 °C … +70 °C

 

Altitude

.......

Up to 2000 m

 

Climatic conditions

.......

5 – 85 % rel. humidity, no condensation

 

External wiring temperature ran

.......

-5 °C … +70 °C

 

Vibration resistance EN 60068-2-6

.......

2…25 Hz ±1.6 mm
25 ... 150 Hz 5 g

 

Galvanic insulation / Test-voltage

.......

Us – Relays, sensors, USB, analog output, Reset input -> DC 3820 V
Relays – sensors, USB, analog output,
Reset input -> DC 3820 V

 

No galvanic insulation

.......

sensors, USB, analog output, Reset input

 

Reset input Y1/Y2

.......

app. DC 18 V / 3,5 mA

 

USB connector

.......

Typ A, for connecting a USB stick configuration / firmware update

 

Housing

Design / Installation Frame

.......

Type V8 / Front mounting kit ER8, 8 TE

 

Dimensions (H x W x D)

.......

140 x 90 x 58 mm, mounting heigth 55 mm

 

Line connection solid wire

.......

je 1 x 1,5 mm2

 

Stranded wire with isolated ferrules

.......

je 1 x 1,0 mm2

 

Torque

.......

0,5 Nm (3,6 lb.in)

 

Protection class housing

.......

IP 20

 

Protection class terminals

.......

IP 20

 

Fitting position

.......

any

 

Mounting

.......

Snap mounting on 35 mm standard rail EN 60715 or M4 screws

 

Weight

.......

app. 360 g

 

Downloads

Datasheet

Operating manual

Operating manual (french)

Operating manual (russian)

Operating manual (spanish)

Site for Programming