Pt 100-Temperature relays Type TR1200
Pt100 Temperature-Relay, 12 Sensors, Interface RS485
Product description
12-channel Temperature-Relay for Sensors Pt100 (RTD)
Temperature relays TR1200 measure the temperature of up to 12 sensors within 199...+850°C and provide the data at an interface RS485 for external evaluation. With its universal power-supply AC/DC 24-240 V it can be connected to all common supply voltages.
The TR1200 provides the data as Modbus-RTU-protocol or according to the ZIEHL-standard. With protocol ZIEHL standard it can replace 2 ZIEHL TR600 relays.
TR1200 itself does not monitor temperatures for limits. For direct monitoring of temperatures our devices with alarms and output relays are recommended.
It is used where temperatures of many sensors Pt100 shall be evaluated by a device with input RS485.
Applications are e.g. monitoring of
- motors and generators (windings, bearings, coolant, ambient temperature)
- transformers (windings, core, ambient temperature)
- machines, plants and equen
Sensors and Displays
- 12 inputs for sensors Pt 100 (RTD)
- Connection 2- or 3-wire
- unneeded inputs can be switched off
- monitoring of sensors for short-circuit an interrupt
- e-digit-display for temperature
- LEDs for assigning the measured value, error, state of relay and interface
Interfaces:
- Interface RS485(protocols ZIEHL standard and modbus RTU)
- Baud rate (4800/9600/19200) and Parity-Bit
- selectable protocols see operating manual on www.ziehl.de
- Relay for error (1 co-contract) for sensor error and operational failure
More features
- easy operation and selection of temperatures at the device
- Sensor-Simulation
- Code protection against manipulation of settings
- Universal supply voltage AC/DC 24…240 V
- Housing for switchgear-mount, 140 mm wide, mounting height 55 mm
- mounting on DIN rail 35 mm or with screws M4 (option)
Software for operation(download from www.ziehl.de)
- software (modbus) for programming the inputs
- Logging function (with connected PC only)
- Hardware for every TR1200: PC with USB or RS232 interface + RS485-USB or RS485-RS232 converter (depending on interface)
- Software: Win7 / Win10, Excel 2010-2016
Technical Data
Rated Supply Voltage Us
AC/DC 24-240 V, 0/45...65 Hz, < 5 VA
DC: 20,4...297 V, AC: 20,4...264 V
Relay output
1 change-over contact (CO)
Type 2, see general technical information
Measuring inputs
12 x Pt100 (RTD) according to EN 60 751 / IEC 60 751
Measuring time sensor
0,25...3s (depending on number of sensors)
Measuring range
-199°...850°C
Resolution
1°C
Tolerance
± 0,5% of value ± 1 K
Sensor-current
≤ 0,8 mA
RS 485 interface
Adress of device
0...96
Baud rate
4800, 9600, 19200 baud
Parity
N, O, E (non, odd, even)
cable-length
max. 1000 m at 19200 baud
Testing conditions
see general technical information
Rated ambient temperature range
-20°C...+65°C
Housing
Design V8
Dimensions (w x h x d)
140 x 90 x 58 mm, mounting height 55 mm
Protection housing/terminals
IP 30 / IP 20
Attachment
DIN-rail 35 mm acc. to EN 60715 or screws M4
Gewicht
ca. 350 g