STW168M

Bus module for controlling up to 8 sliders in extraction systems

Share: Facebook   WhatsAppWhatsApp   E-Mail

Part number

S225544

Product description

 

Bus module for controlling sliders in extraction systems

Technical Data

Rated supply

Rated supply voltage Us

.......

DC 24 V, SELV, PELV

 

Tolerance

.......

DC 20 - 30 V

 

Power consumption

.......

< 3,5 W

 

Imax Bus line

.......

< 10 A

 

Switch on time

.......

100 %

 

Relay output K0...K7

.......

8 x 1 Wechsler, gemeinsame Wurzel

 

Switching voltage

.......

max. AC 300 V; DC 300 V

 

Switch on current closer (NO)

.......

AC 15 A 4 s 10 % ED

 

Minimum voltage/current

.......

12 V 10 mA

 

Conventional thermal current Ith

.......

max. 5 A

 

Total current on terminal 05

.......

max. 5 A

 

Switching capacity max. AC cos phi = 1

.......

1500 VA

 

Inputs I0...I7

.......

Current transformer STWA1(H), potential free contacts or Current sensor type S1

 

Internal resistant

.......

approx. 15 kOhm

 

Overload with STWA1(H)

.......

max. 100 A continuous, max. 300 A  10 s

 

Installation conditions

permissible ambient temperature

.......

-20°C…+55°C

 

permissible storage temperature

.......

-20°C…+70°C

 

Mounting

.......

< 2000 m see level

 

Climatic conditions

.......

5 - 85 % rel. F., no condensation

 

Shaking safety EN 60068-2-6

.......

2...13,2 Hz +/- 1 mm  13,2...100 Hz 1 g

 

Housing

Housing / Installation Frame

.......

Design V6 / Front counting kit ER6, 6 TE

 

Mounting height

.......

58 mm

 

Dimensions (w x h x d) mm

.......

105 x 90 x 58 mm

 

Cable connection solid

.......

1 x 0,34 - 2,5 mm2 / AWG 22-12

 

Finely stranded with end sleeve

.......

1 x 0,34 - 2,5 mm2 / AWG 22-12

 

Stripping length / torgue

.......

8 mm / 0,5 Nm

 

Attachment

.......

Snap on mounting on standard rail 35 mm according to EN 60 715 or screws M4 (additional bolts are not included)

 

Protection housing / terminals

.......

IP 30 / IP 20

 

Weight

.......

approx. 250 g