STW168M
Bus module for controlling up to 8 sliders in extraction systems
Product description
Bus module for controlling sliders in extraction systems
Technical Data
Rated supply
Rated supply voltage Us
DC 24 V, SELV, PELV
Tolerance
DC 20 - 30 V
Power consumption
< 3,5 W
Imax Bus line
< 10 A
Switch on time
100 %
Relay output K0...K7
8 x 1 Wechsler, gemeinsame Wurzel
Switching voltage
max. AC 300 V; DC 300 V
Switch on current closer (NO)
AC 15 A 4 s 10 % ED
Minimum voltage/current
12 V 10 mA
Conventional thermal current Ith
max. 5 A
Total current on terminal 05
max. 5 A
Switching capacity max. AC cos phi = 1
1500 VA
Inputs I0...I7
Current transformer STWA1(H), potential free contacts or Current sensor type S1
Internal resistant
approx. 15 kOhm
Overload with STWA1(H)
max. 100 A continuous, max. 300 A 10 s
Installation conditions
permissible ambient temperature
-20°C…+55°C
permissible storage temperature
-20°C…+70°C
Mounting
< 2000 m see level
Climatic conditions
5 - 85 % rel. F., no condensation
Shaking safety EN 60068-2-6
2...13,2 Hz +/- 1 mm 13,2...100 Hz 1 g
Housing
Housing / Installation Frame
Design V6 / Front counting kit ER6, 6 TE
Mounting height
58 mm
Dimensions (w x h x d) mm
105 x 90 x 58 mm
Cable connection solid
1 x 0,34 - 2,5 mm2 / AWG 22-12
Finely stranded with end sleeve
1 x 0,34 - 2,5 mm2 / AWG 22-12
Stripping length / torgue
8 mm / 0,5 Nm
Attachment
Snap on mounting on standard rail 35 mm according to EN 60 715 or screws M4 (additional bolts are not included)
Protection housing / terminals
IP 30 / IP 20
Weight
approx. 250 g