Residual Current Monitor RCM1000V
Residual Current Monitor for AC-currents in grounded power supply systems
Product description
RCM1000V RCM100V monitors residual currents in grounded power supply systems. Used as a current relay it monitors AC- or pulsing DCcurrents for exceeding upper or lower limits. Insulation faults can be caused by damages (mechanical, thermic or chemical) of insulations or also by humidity or pollution. At currents > app. 250 mA (at 230 V) at a location, the fault can lead to danger of fire.
Applied as current relays RCM1000V can among others monitor current in the neutral conductor. Nonlinear loads, e.g. switching power supplies in PC, printers or lights with EGC, cause harmonics in the neutral conductor: Even when the load is symmetric, the harmonics can lead to an overload in the neutral conductor. RCM1000V detect and report this overload.
Residual current monitors detect these faults in widely branched power supply systems and make a signal before additional damage develops. By displaying the residual current also stealthy changes can easily be detected and localized by switching on and off parts of the power supply system.
Particularly useful in monitoring in systems in which no fault current circuit breaker can or shall be used, because an immediate switching would have wideranging consequences, such as breakdown of computersystems or interruption of processes of sensitive goods. RCM1000V do NOT replace fault current circuit breakers for protection from electric shock but they can complement it by detection an fault in the insulation before the systems has to be shut off.
- Monitoring of residual currents
- 2 limits for alarm and trip
- Monitoring of current, 2 x under- or overcurrent or windows
- Measuring range 0,003 … 9,999 A
- Setting range 0,010...9,999 A
- Display can be scaled
- Test-button and automatic test every 24 hours
- Input for current transformer STWA3D with monitoring of transformer
- Start-up delay to suppress alarms when switching on
- 4 digits bright LED-display for measured values and programming
- LEDs for alarms, state of relays and units
- Limit, hysteresis, switching delay and switch off delay individually programmable
- Function of relays (nc-, or no-mode) and interlocked switching or autoreset programmable
- Universal supply voltage AC/DC 24-240 V
- Housing for DIN-rail mount, 70 mm wide, mounting height 55 mm
- Accessory: Front mounting kit type ER4
Technical Data
AC/ DC 24V - 240V, < 1,5W, < 5 VA
DC 20,4 - 297 V, AC 20-264 V 50 ...500 Hz
2 x 1 co-contacts, type 2, see general technical informations
Monitoring of current (program 1 and 2)
External transformer
Type STWA3D... (20, 35, 70, 125)
Cable for external transformer
≤ 10 m, single wire, ≥ 0,75 mm2
Measuring range
.......
0,003 A ... 9,999 A
Hysteresis alarm 1/alarm 2
10 % ... 25 %
Rated frequency range
50 ...500 Hz
Startup delay power on
adjustable 0 ... 10 s
Delay alarm on
adjustable 0,03 ... 10,0 s (Prog. 2 = 0,03 ... 500,0 s)
Delay alarm off
adjustable 0 ... 999 s
Residual current relay ( program 1 only EN 62020)
Rated residual operational current (Ion)
Alarm 2 -> adjustable 0,010 A ... 9,999 A
Alarm 1 -> adjustable 50% ... 100% of alarm 2
Switching limits for alarm 1/alarm 2
0 ... -20%
Function at loss of supply voltage Us
depending of configuration of relays:
closed current -> relays release = alarm
operating current -> relays remain released (= no
alarm)
Response characteristic
Typ A
Current relay ( program 2 only)
Monitoring range alarm 1 / alarm 2
0,010 A ... 9,999 A
Hysteresis alarm 1 / alarm 2
10%...25%
Accuracy 50/60 Hz
± 2%, ± 3 digit
Accuracy > 60 Hz
± 10%, ± 3 digit
Insulation (EN 60664-1)
Rated impulse withstand voltage
4000 V
Rated insulation voltage (Ui)
AC 300 V
Overvoltage category
III
Contamination level
2
EMC tests (EN 62020)
Emitted interference
EN 61000-6-3
Burst
EN 61000-4-4 ± 4 kV pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms
Surge
IEC 61000-4-5 ± 2 kV
Electrostatic discharge
IEC 61000-4-2 ± 3,8 kV discharge contact,
± 6 kV discharge air
Rated ambient temperature range
-20...+65 °C
Storage temperature
-20...+70 °C
Housing
Design
V4, 4 TE, mounting height 55 mm
Dimension (w x h x d)
70 x 90 x 58 mm
Protection housing/terminals
IP30/20
Installation
Snap mount on standard rail 35 mm acc. to EN 60715 or screws M4
Weight
app. 170 g