Measuring-Transducer Type MU1001K
Universal Measuring Transducer for DC voltage and DC current, isolation amplifier, scaleable
Product description
Universal Measuring-Transducers MU1001K can measure DC-signals up to 300 V. Inputs 60/150/300 mV measure direct current. Pre-set measuring-ranges can be selected by the user. More measuring-ranges (zero and full scale) can be easily scaled. The output-signals DC 0/2-10 V and 0/4-20 mA are insulated from measuring-input and supply-voltage.
With its universal power-supply AC/DC 24-240 V the measuring-transducer can be connected to all common supply-voltages.
Overview of functions
- Output signal 0-20mA and 0-10V or 4-20mA and 2-10V
- Rated Supply Voltage AC/DC 24-240V
- Insulation between inputs, outputs and supply voltage
- Standard ranges adjustable, universally scalable input ranges
Inputs
- DC -300 … 300 mV (preset values: 0…60 / 0…150 / 0…300 / -60…60 / -150…150 / -300…300 mV)
- DC -10 … 10 V (preset values: 0…10 / 2…10 / -10…10 V)
- DC 0 … 300 V (preset values: 0…20 / 0…50 / 0…100 / 0…200 / 0…300 V)
Zeros and Full Scales for more measuring-ranges can be freely selected by the user.
Technical data
Rated supply voltage Us
AC/DC 24 – 240 V 0/50…400 Hz < 3 W < 8 VA
Tolerance
DC 20,4 - 297 V
AC 20 - 264 V
Output (2 outputs with common ground)
Response-time T09
< 40 ms
Voltage output
DC 0/2 – 10 V
Tolerance
0,3 % of full scale (from 0,1 V)
Temperature factor
< 0,01 % / K
Resolution
11,6 Bit < 3,1 mV
Load
≥ 1 k Ω
Current output
DC 0/4 – 20 mA
Tolerance
0,3 % of full scale (from 0,1 mA)
Temperature factor
< 0,015 % / K
Resolution
11,6 Bit < 6,1 μA
Load
Load
Error from load
(250 Ω – resistance) / 250 Ω * 0,3 % of final value
Test conditions (EN 61010-1)
Rated supply voltage Us (terminals A1,A2)
Pollution degree
2
Overvoltage category
III reinforced insulation
Rated insulation voltage Ui
300 V
Input (terminals 4,5,6,7)
Pollution degree
2
Overvoltage category
II reinforced insulation
Rated insulation voltage Ui
300 V
Galvanic insulation / Test-voltage
input – output
DC 3540 V
Us – output
DC 3540 V
Us – input
DC 3540 V
Environmental conditions
Ambient temperature range
-20 °C ... +65 °C
Storage temperature range
-20 °C ... +70 °C
External wiring temperature range
-5 °C ... +70 °C
Altitude
< 2000 m
Climatic conditions
5 – 85 % rel. humidity, no condensation
Vibration resistance EN 60068-2-6
2…13,2 Hz ±1 mm
13,2 ... 100 Hz 1 g
Housing (Type K)
Dimension (H x W x D)
75 x 22,5 x 110 mm
Line connection solid wire
each 1 x 0,5…2,5 mm2
Stranded wire with insulated ferrules
each 1 x 0,14…1,5 mm2
Torque
0.5 Nm (3,6 lb.in)
Protection class housing
IP 40
Protection class terminals
IP 20
Mounting
Snap mounting on 35 mm standard rail EN 60 715 or M4 screws
Weight
app. 100 g
CAD Data
Certificates
FAQ / Product videos