Frequency- and Speed Relay FRMU1000 / FR1000
Frequency- and Speed Relay
with integrated Measuring Transducer
Part number
Product description
The FRMU1000 is a speed-monitor, a frequency-monitor and a measuring-transducer in one device.
2 limits with 1 relay each can be programmed for under- or overspeed, under- or overfrequency or each monitoring of a range (min/max).
The input for monitoring of speed can evaluate signals from proximity-sensors 2- or 3-wire, npn- or pnp. The display can be scaled. Thus the real speed of a shaft can be displayed, even though there are several pulses per revolution, e.g. from a cogwheel.
Application as Frequency-Relay
Monitoring of frequencies in mains 16 2/3 to 400 Hz on maintaining a range (min/max).
Application as Speed-Relay
Monitoring of overspeed or underspeed, each with pre-alarm and alarm, monitoring of maintaining a range (min/max) or monitoring of stop at machines and equipment, e.g. at conveyors, escalators or lifts or for monitoring of drive-belts.
Applications as Measuring Transducer (FRMU only)
In addition, the FRMU can be used as measuring-transducer to convert the input-signal into a standard-signal 0/4-20 mA or 0-10 V.
Function
Frequency
- Measuring-inputs voltage AC 20-200 V/80-440 V or AC110-300V/210-830 V (option)
- Monitoring of frequency of own supply-voltage
- Monitoring range 10...500 Hz
- Resolution of display 0.01 Hz
Speed
- Monitoring range 5...99999 1/min
- Display can be scaled
- Measuring input for capacitance-switches 2- or 3-wire, PNP or NPN
- Start-up-delay programmable
- Start-input (activates device with switching on the monitored drive)
General
- Setting in Hz oder 1/min
- 5-digit display
- Analog output DC 0/4-20 mA or DC 0-10 V, free scaleable (with isolation to frequency-input U1/U2)
- 2 limits/ 2 relays
- programmable for each relay:
- Monitoring of min, max or range
- Hysteresis
- Autoreset reclosing lock
- Delay-time for switching an switching back down to 50 ms
- Operating- or closed-current mode
- LEDs for state of relays and unit (Hz oder min-1)
- Storage of min- and max-values of the inputs
- Easy setting with 3 buttons
- Code lock against manipulatin of settings
- Universal power supply AC/DC 24-240 V
- Terminals pluggable
Technical data
Rated supply voltage Us
AC/DC 24-240 V, <3W, <10VA
(AC 20-264 V, DC 20,4-297 V)
Frequency
0, 40...500 Hz, ab AC 80 V: 10...500 Hz
Measuring input Frequency
10.00 - 500.00 Hz
Admissible voltage
AC 20-200 V/ 80-440 V oder
AC 110-300 V/ 210-830 V (Option)
Measuring input Speed
5-99999 min-1
PNP oder NPN, 3-wire or 2-wire
Analog output
0/4-20 mA, max. 500 Ω,
0-10 V, max. 10 mA
max. error
< 0,15 % from FullScale+ 0,015 %/K
Relais output
Type 3, see general technical information
2 x 1 (change-over) contact
Test conditions
see general technical information
Rated ambient temperature range
-20 °C ... +60 °C
Housing
Dimensions H x W x D
Design V4: 90 x 70 x 58 mm, mounting height 55 mm
Protection housing/terminals
IP 30/IP 20 (Terminals pluggable)
Attachment
on 35 mm DIN rail or with screws M4
Weight
approx. 180 g
Certificates